Boiler Data
Steam Output
8,487 lbs/hr from and at 212 degrees F
Emissions
60 PPM Low NOx Burner
Fuels
Natural Gas and Light Oil
Connections
City Water
1 1/2” NPT
Natural Gas
2” Flanged
Fuel Oil Supply
3/4” NPT
Fuel Oil Return
3/4” NPT
Steam
6“ 300# Flanged
Requirements
Electrical
75 AMPS @ 460/3/60HZ
Atomizing Air
Air Compressor, Included
Instrument Air
Not Required
Fuel Oil Pump
Included
Stub Stack
Included
Gas CFH (1,000 BTU)
9,900 CFH
Gas Pressure
5-10 PSIG w/ Regulator, 1-3 PSIG w/o
Light Oil GPH (140,000 BTU/gallon)
71 GHP
City Water
65 gallons per minute, 40-70 psig
Water Softener
Included
Chemical Feed Tank
Included
Blowdown Separator
Included, with aftercooler
Boiler Feed Tank with Preheater
Included