Boiler Data
Steam Output
12,075 lbs/hr from and at 212 degrees F
Emissions
60 PPM Low NOx Burner
Fuels
Natural Gas and Light Oil
Connections
City Water
2” NPT
Natural Gas
4” 150# Flanged
Fuel Oil Supply
3/4” NPT
Fuel Oil Return
3/4” NPT
Steam
4“ 300# Flanged
Blowdown Drain
4” 150# Flanged
Requirements
Electrical
100 AMPS @ 460/3/60HZ
Atomizing Air
Air Compressor, Included
Instrument Air
Not Required
Fuel Oil Pump
Included
Stub Stack
Included
Gas CFH (1,000 BTU)
14,644 CFH
Gas Pressure
5-10 PSIG
Light Oil GPH (140,000 BTU/gallon)
104.6 GHP
City Water
55 gallons per minute, 40-55 psig
Water Softener
Included
Chemical Feed Tank
Included
Blowdown Separator
Included, with aftercooler